natural gas generator set

With silencer, it can run for a long time at an ambient temperature of 40 degrees, meeting the purchaser’s acceptance standard.

Category:

Description

Parameters of natural gas generator set

 

Unit model Reserve power (kW) Engine brand Engine model Generator brand Generator model
KMS-500 550 Cummins power KMS-500 Cummins power TFW-500
scope of supply Engine, generator, shock absorber, (AMF) control panel, muffler, exhaust pipe, factory-related technical documents, certificates, batteries, wearing parts, consumables and simple packaging.
Unit function The generator set is equipped with AMF control panel and large-screen LCD display, which can detect and display the electrical parameters and non-electrical parameters of the generator set, such as power generation (three-phase voltage, three-phase current, frequency, power, power factor, accumulated electric energy, etc.), engine parameters (water temperature, oil pressure, rotating speed, etc.), battery voltage, running time, accumulated starting times and other parameters.

Protection function: The control system has alarm and protection functions for abnormal power generation (high voltage/low voltage, high frequency/low voltage, overload), high water temperature, low oil pressure, overspeed, low battery voltage, overcurrent and charging failure.

99 groups of historical records can be saved circularly, and can be queried on site.

Gas generator set data
model KMS-500 starting system 24V electric start-up
Power factor COSφ=0.8 (lag) Output voltage (v) 400
Connection mode Three-phase four-wire “Y” Frequency (HZ) 50
Reserve power (kW) 550 Rated current (a) 900
Engine data
model KMS-500 Maximum power (kW) 550
Rated speed (rpm) 1000 Rated power (kW) 500
Cylinder diameter/stroke (mm) 190/155 Cylinder arrangement 12-cylinder V type
Gas consumption (m³/kw.h) 0.3 lubricating system forced lubricating
Air intake mode Supercharged intercooling Cooling mode Closed cooling
Compression ratio 10.5:1 Displacement (l) 30
Requirements for fuel (percentage is volume percentage)
Fuel type natural gas Methane content CH4(%) >70
Carbon dioxide content (%) ≤30 Nitrogen content (%) ≤5
Hydrogen content (%) ≤1 Oxygen (%) ≤0.4
Sulfur content (ppm) ≤25 Mixed gas formation mode preblend
Gas source pressure (kPa) 2.7-4 Gas calorific value (MJ/m) ≥20.8
Generator data
Generator brand Cummins power model TFW-500
Rated capacity (KVA) 625 Excitation mode brushless
Insulation grade H the protection grades IP22
Voltage adjustment range ≥±5% Steady-state voltage regulation rate ≤±1%
Efficiency (100% load) 91.7% Voltage control mode AVR
Control cabinet data
Control module brand SMARTGEN
Performance and characteristics of control cabinet Large screen liquid crystal (LCD) display, optional Chinese and English display, touch button operation.

It can monitor and display voltage, frequency, power, power factor, speed, oil pressure, water temperature, battery voltage and running time in real time.

It has perfect functions such as fault display protection. The automatic start and stop of the generator set can be controlled by the remote power-on signal.

 

Additional information

brand

Cummins power

Common power (KW)

500

quantity

2 sets


Contact Us